Key Features

  • Communication boards available for RS232, RS485, USB, Ethernet.

  • Usable in all 1/8 DIN size Laureate DPMs, counters, timers & remote displays.

  • Serial communication boardssupport Modbus RTU and Custom ASCII protocols.

  • Ethernet communication boards support Modbus TCP.

  • User-selectable baud rates to 9600

  • Converter boards connect a USB or Ethernet line to the host meter and an RS485 bus with up to 31 remote meters.

  • Powered by instrument or USB line.

  • Communications isolated from meter and power grounds

Description

Meter connection to PC via an RS232 or USB serial cable.A communication option board allows a Laureate digital panel meter, counter or timer to be interfaced to a PC for programming via Laurel's Windows-based Instrument Setup Software, or to output readings to a remote PC, PLC or other device with a communication port. The transmitted data may include the latest reading, peak value, valley value, alarm status, and setup information. The data can then be displayed, processed and data logged. The data can also be received by a Laureate 6-digit remote display, which can display the serial data, control relay outputs, and generate a scaled, isolated 4-20 mA, 0-10V or -10V to +10V analog output.

If the primary objective is to program a meter directly from a PC using Instrument Setup Software, a USB interface board is recommended. Once the meter has been programmed, the interface board can be removed if no longer needed.

 

If the objective is to connect a network of meters to a PC, our USB 2.0-to-RS485 converter board can be used. That board can be connected to a PC via a USB port, and also act as the server for up to 31 meters on an RS485 bus via RJ11 connectors. The remote meters must be equipped with Laurel's RJ11 RS485 interface board. That board features dual RJ11 connectors wired in parallel for RS485 daisy-chaining using commercial 6-wire RJ11 data cables, with no need for a hub. Please see our cables page.

 

If the objective is to connect meters to an existing Modbus RS485 bus, either of two RS485 interface board can be selected. Both boards are fully compatible with the Modbus RTU protocol, as are all other Laureate serial interface boards. Our RJ11 RS485 interface board uses dual RJ11 connectors wired in parallel for daisy chaining, while our RJ45 RS485 interface board uses dual RJ45 connectors wired in parallel for daisy chaining.

 

 

If the objective is to connect a meter to an Ethernet LAN, our Ethernet interface board allows a meter to be connected to an available router port using a standard Ethernet cable. Our Node Manager software and Instrument Setup software makes node discovery and setup exceptionally simple.

 

If the objective is to connect a network of meters to an Ethernet LAN, our Ethernet-to-RS485 converter board should be selected. That board can be connected to an Ethernet LAN utilizing a single Ethernet cable and also act as the server for up to 31 meters on an RS485 bus via RJ11 connectors. The remote meters must be equipped with Laurel's RS485 interface board. The Ethernet-to-RS485 converter board features dual RJ11 connectors for RS485 daisy-chaining using commercial 6-wire RJ11 data cables, with no need for a hub.

Three communication protocols are user-selectable:

  • Custom ASCII is a text string based protocol and is recommended if the only devices on theserial communications data line are Laureate meters. It supports up to 31 digital addresses. It is not compatible with Ethernet.

  • Modbus RTU is an international master / slave communications standard and allows Laureates to share the same RS485 data lines with non-Laurel devices. It supports up to 247 digital addresses.

  • Modbus TCP is Modbus RTU seamlessly converted to TCP/IP packets by our Ethernet Nodes.

 

Specifications

Electrical Specifications

Electrical Safety & Isolation

Isolation

250V rms working, 2.3 kV rms per 1 min test

ESD Protection

15 kV per IEC 1000-4-2

EMI Immunity

10 V/m per IEC 1000-4-3

EFT Protection

2 kV per IEC 1000-4-4s

Short Circuit Protection

Continuous

Selectable Protocols

Modbus RTU / TCP, Custom ASCII

Protocol Specifications (protocols reside on Main Board)

Modbus RTU/TCP

Standards Compliance

Modbus over Serial Line Specification V1.0 (2002)

Protocol Type

Master-slave, query-response command mode

Data Streaming Mode

Not supported by Modbus specification

Data Formats (selectable)

1. No parity, 8 data bits, 2 stop bits

 

2. Odd parity, 8 data bits, 1 stop bit

 

3. Even parity, 8 data bits, 1 stop bit

Applicable Interface Boards

RS232, RS485, USB, Ethernet, Ethernet-to-RS485, USB-to-RS485

Main Board Revision Level

Level 5 or above

Custom ASCII

Standards Compliance

Laurel proprietary protocol

Data Format

No parity, 8 data bits, 1 stop bit

Protocol Type

Text string based command mode or continuous data streaming mode

Data Sreaming Mode

User selectable up to 60 readings/sec

Applicable Interface Boards

RS232, RS485, USB

Main Board Revision Level

Any

 

Đồng hồ đo kỹ thuật số, bộ đếm và bộ hẹn giờ Laurels cung cấp tùy chọn dữ liệu RS232, RS485, USB hoặc Ethernet. Bo mạch LNET485 giao tiếp liên kết Ethernet tạo sự kết hợp của tối đa 31 đồng hồ đo và bộ phát; chúng được kết nối nhiều lần trên một bus RS485 bán song công hoặc song công toàn phần.

Bộ phát dòng Laurels LT có tiêu chuẩn với cổng nối tiếp RS232-RS485, trong khi bộ phát dòng LTE có tiêu chuẩn với cổng Ethernet. Đầu ra tương tự 4-20 mA cách ly cũng là tiêu chuẩn cho đầu ra tới PC hoặc PLC.

Việc khám phá và cấu hình các nút Ethernet Laurels và các thiết bị được kết nối của chúng thông qua Phần mềm quản lý nút dựa trên Windows hoặc thông qua Chế độ máy chủ trang web sử dụng một web mỗi nút.